Centauri
®
CONDENSINGWATERBOILER
INSTALLATION & MAINTENANCE MANUAL
Models (1500, 1800, 2000) WB 250A-IFC
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND
MAINTENANCE OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER
PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS
UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain
important information that will help you in maintaining and operating this appliance.
Riverside Hydronics
®
, LLC
990 Haltom Road
Fort Worth, Texas 76117
1-800-990-5918
www.riversidehydronics.com
Przeglądanie stron 0
1 2 3 4 5 6 ... 39 40

Podsumowanie treści

Strona 1 - Centauri

134-52 07/13 Centauri®CONDENSINGWATERBOILERINSTALLATION & MAINTENANCE MANUAL Models (1500, 1800, 2000) WB 250A-IFC Installation an

Strona 2

1034-52 07/13 5.5 Temperature Control Sensor The Temperature Control Sensor is coiled and secured to the control enclosure along with the Senso

Strona 3

1134-52 07/13 6.3 Gas Piping Size: Use the values in “Convert Fittings To Equivalent Straight Pipe” to add the equivalent straight pipe for each el

Strona 4 - PRODUCT SAFETY INFORMATION

1234-52 07/13 6.4 Appliance Isolation during Gas Supply Piping Pressure Test 1. The appliance and its provided manual shutoff valve must be disc

Strona 5

1334-52 07/13  All Air From Inside The Building: Each opening requires a minimum free area of 1 square inch per 1000 Btu/hr input, but not less

Strona 6

1434-52 07/13 7.3 Remote Combustion Air Cap A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent ter

Strona 7

1534-52 07/13 8.3 Maximum Category IV Vent Length (Equivalent Length) A vertical or horizontal remote Category IV vent system must be used wi

Strona 8

1634-52 07/13 8.5 Combining Category IV Vents Combined Centauri or Centauri Plus Category IV gas vent systems must incorporate an Exhausto or Tj

Strona 9

1734-52 07/13  Thermal Expansion A relief valve that discharges periodically may be due to thermal expansion in a closed system by components,

Strona 10 - 34-52 07/13

1834-52 07/13 10 TEMPTRAC™ ELECTRONIC CONTROLLER PANEL 10.1 Principle Of Operation The boiler operates to satisfy the setpoint of the TempTrac

Strona 11

1934-52 07/13 LABEL DEFAULT VALUE NET TEMPERATURE NET TEMP DETERMINED BY St1 165 165°F LED display value Hy1 -8 157°F St1 + Hy1 St4 -10 15

Strona 12

234-52 07/13 TABLE OF CONTENTS 1. Safety Considerations 2. Standard Features and Equipment 2.1. Performance 2.2. Burner, Combus

Strona 13

2034-52 07/13  C to D: Once modulation is established, the sensed loop temperature can fluctuate between 155°F and 145°F (between St4 and SR). Th

Strona 14

2134-52 07/13 10.9 LED Display Alarm Messages Alarm messages are displayed in the upper LED readout and alternate with the default display. An ala

Strona 15

2234-52 07/13 11.3 BAS connection over network with MODBUS RTU protocol (requires option ALMMB)  An optional serial connection cable (part no.

Strona 16

2334-52 07/13  Factory Default Settings - The values of the Outdoor Reset and Warm Weather Shutdown functions in the TempTrac control’s paramete

Strona 17

2434-52 07/13 12 SEQUENCE OF OPERATION 1. Incoming 120VAC a. Full time power to the Main Control Switch b. Full time power to the Variable Fr

Strona 18

2534-52 07/13 8. Delay-On Relay - Once the Delay-On (Low Fire Hold) Relay has timed out, it energizes the Modulation Release Relay (SPDT) to enable

Strona 19

2634-52 07/13 13 INITIAL STARTUP 13.1 Initial Startup Requirements Installation should be complete prior to performing initial startup; and the

Strona 20

2734-52 07/13 c. Reattach the manometer to the gas train manual shutoff valve at the burner and record the measured gas pressure in inches of wate

Strona 21

2834-52 07/13 20. After the pre-purge, the flame control energizes the HSI for the heat up period, approximately 30 seconds. At the end of that pe

Strona 22

2934-52 07/13 INLETPRESSUREMANIFOLDPRESSUREVALVE ORIFICEADJUSTMENTREGULATORADJUSTMENT Gas Train Illustration REGULATORADJUSTMENTHIGH GAS PRES

Strona 23

334-52 07/13 Warranty Forms & Wiring Diagrams Ship Separately With Each Product 9. Operatin

Strona 24

3034-52 07/13 14 TROUBLESHOOTING GUIDE Problem Probable Cause Corrective Action Starting or Pre-purge Failure Power Supply Check fuse and/o

Strona 25

3134-52 07/13 15 REPLACEMENT PARTS REPLACEMENT PARTS

Strona 26

3234-52 07/13 15.1 Control Panel 

Strona 27

3334-52 07/13 15.2 Control Panel Components (Optional components may not be included) Key No. Part No. Description Qty. U/M 1 101947 CONTROL

Strona 28

3434-52 07/13 15.3 Burner Assembly

Strona 29

3534-52 07/13 15.4 Burner Assembly and Gas Train Components Optional components may not be included) Burner Assembly Components Item Qty

Strona 30

3634-52 07/13 16 PERIODIC MAINTENANCE Listed below are items that must be checked to ensure safe reliable operations. Maintenance must be performed

Strona 31 - 15 REPLACEMENT PARTS

3734-52 07/13 6. The combustion air filter should be replaced every six months. If filter blockage becomes excessive the filter safety switch will

Strona 32 - 15.1 Control Panel

3834-52 07/13 17 RECOMMENDED MAINTENANCE SCHEDULE 1. Annual Maintenance a. Check all joints and pipe connections for tightness, corrosion or dete

Strona 33

3934-52 07/13

Strona 34 - 15.3 Burner Assembly

434-52 07/13 1. SAFETY CONSIDERATIONS  WARNING: If the information in the supplied manual(s) is not followed exactly, a fire, explosion or expos

Strona 35

4034-52 07/13 Riverside Hydronics, LLC  990 Haltom Road  Ft. Worth, TX 76117  1‐800

Strona 36

534-52 07/13 2. STANDARD FEATURES AND EQUIPMENT 2.1 Performance  Up to 94% efficiency at low fire with low return temp  Inward-fired burner t

Strona 37 - NOMINAL FILTER SIZE

634-52 07/13 3 PRODUCT DESCRIPTION Component, Controls and Connection Locations (Locations May Vary)

Strona 38

734-52 07/13 4 BOILER INSTALLATION 4.1 Checking Equipment Before You Install Inspect the unit completely upon receipt from the freight carrier

Strona 39

834-52 07/13 4.6 Clearances To Combustible Surfaces Minimum 1" clearance must be provided from any vent surface to adjacent combustible m

Strona 40 - Riverside Hydronics

934-52 07/13 1. Installing the boiler on a 4 inch to 6 inch housekeeping pad is recommended to ensure proper condensate drainage. 2. Use 3/4” CP